Application:
Inductive proximity switches
are capable of controlling contactors, relays or electronic
logic switching systems. They are used as control or monitor
switches on conveyor and crane systems, transfer lines and
machine control systems, and to solve general automation
problems.
Actuation:
Proximity switches are
actuated by metals approaching or traveling past the active
switching surface. The switches can be actuated through
non-metallic substances such as glass, plastic or rubber. They
are not affected by oil, water or dust.
Definitions:
Nominal switching
distance Sn:
The nominal switching
distance refers to a switching plate of steel St37 (the size of
the switching plate should be taken form the individual
description). It is reduced in the case of nickel by
approximately 15%, in the case of brass by approximately 45%, in
the case of aluminum by approximately 50% and in the case of
copper by approximately 55%.
Real switching distance
Sr:
The rear switching distance
takes into account permissible manufacturing tolerances.
Effective switching
distance S:
The effective switching
distance takes into account the permissible variation over the
entire temperature range as well as the manufacturing
tolerances. S
£ 0,81 x Sn
Reproducibility:
Reproducibility of
consecutive switching cycles is determined over a period of 8
hours with a housing temperature of 15°C
- 30°C
and a voltage of En
± 5%. The variation
of any two measurements will not exceed the value stated in the
specification.
Hysteresis:
This is the difference
between the operating point and the release point of a proximity
switch.
Resistance to sustained
short circuit:
Switching resistance to
sustained short circuit are not destroyed even in the event of
sustained short circuit because the output stage is disconnected
electronically
Fitting
instructions
Flush fitment Non-flush fitment

|
Fitting instructions for
tandem arrangement

Measuring plate
Measuring
plate steel St37
N14.. to N70.. 100% = N²
Example: N30-..-..-.. Measuring plate. 30x30mm
N200.. to N1200.. 100% = 150x100x2 mm
Standard
value
|
Target size % |
150 |
50 |
25 |
12,5 |
|
Deviation from Sn in % |
+10 |
-15 |
-25 |
-45 |
General specification:
Protection Class: IP 65 ( DIN 40050 f)
Ambient Temperature
Type N...- -20°C
to +80°C
Type
NC...- -20°C
to + 100°C
NAMUR
Type NC...-1-.. -20°C
to + 125°C
Cable: 2m LIYY 0,75mm²
special cable and extra length available
Hysteresis: 1 to 5%
Repeatability:
£1%
Example of order:
N150-95-L83-100 L=2m

 |